Licensee Login

Tests

ID

Test Type

Tests

Results

Lab

1

Combustibility
Twenty-Flve Foot
Tunnel Furnace Test

ASTM E-84-8la

 

Flame spread value 0
Smoke density factor 0
Fuel contribute 0
Test extended to 30 minutes

Hardwood Plywood Manufacturers Association Tested in P .0. BOX 2789
Reston, Virginia 22090
Main Office: 665 Rodi Road, Suite 305
Pittsburgh, PA 15235
Phone 412/244-0440 Fax: 412/244-9090
Email: info@hardwood.org
https://hmamembers.org/

2

Fire Proof

2 hr Test

ASTM E814 / UL 1479
CT State Building Inspector
New York City MEA 68-91-M
The initial ambient temperature was 57°F. Hose Stream Test: No holes formed in the unexposed side of the
sample after being exposed to the hose stream for 24 seconds.
F Rating: 120 minutes
The sample met the acceptance criteria of the "F Rating" for 120
Minutes per ASTM E814/UL 1479 specifications.

V-TEC Lab Inc.
212 Manida Street
Bronx, NY 10474 USA
Phone: 718-542-8248 Fax: 718-542-8759
Email: Neil@vteclabs.com Contact: Neil Schultz
http://www.vteclabs.com/

3

Formaldehyde & VOC Test ASTM D5116
Connecticut
Maryland
The emissions test results indicate that neither formaldehyde nor volatile organic compounds are emitted from the airKrete insulation at 24 hours and 96 hours from manufacture.

ORTECH Environmental
804 Southdown Road
Mississauga, Ontario, Canada L5J 2Y4
Phone: 905.822.4120 Toll-free: 1.877.774.6560 Fax: 905.855.0406
Email: info@ortech.ca
http://www.ortechenvironmental.com/

4

Mold Growth Test ASTM Guideline D 6329-98 Results show that the AirKrete Insulation Sample was resistant to mold growth at both 75% and 95% relative humidities. Neither molds were found to amplify in the materials at either humidity.

Air Quality Sciences
1337 Capital Circle
Marietta Georgia 30067
Phone: 770-933-0638 Fax: 770-933-0641

5

Shrinkage Test ASTM C951 No Shrinking - After spraying 40 days at 75% and 50% relative humidity

Twin City Testing
662 Cromwell Ave
St. Paul, MN 55114
Phone: 651/645-3601
http://www.twincitytesting.com/

6

Sound Test ASTM E90 For any pair of rooms and microphone system, the 95% confidence interval TL, for transmission loss must be less than the following. Range of Transmission Loss One-Third Octave Uncertainty, dB Bands Required Actual
125 and 160 3 <1.5
200 and 250 2 <1.5
315 - 4000 1 <1

INTERTEK
Intertek Testing Services NA inc.
3933 US Route 11
Cortland NY 13045
Phone: 607-758-6572 Fax: 607-330-8006
http://www.intertek.com/

7

Thermal Conductivity Test

ASTM C518-Challenges



ASTM C518

Thermal Conductivity

Dynalene Inc. Laboratory
5250 W. Coplay Rd. Whitehall, PA 18052
Ph: 610-262-9689 Fax: 610-262-7437

8

Water Permeability Test ASTM E96 / E96M - 10 0.3701cm/S Standard Test Methods for Water Vapor Transmission of Materials

V-TEC Lab Inc.
212 Manida Street
Bronx, NY 10474 USA
Phone: 718-542-8248 Fax: 718-542-8759
Email: Neil@vteclabs.com Contact: Neil Schultz
http://www.vteclabs.com/

The airkrete specifications
The airkrete MSDS file